GDYD-2030A 30kVA.200kV Automatic AC/DC Hipot Test Set
●7inch mtundu LCD chophimba, ndi PLC ulamuliro zochita zokha.
●HV Voltage, LV voltage, LC yapano yoyezedwa nthawi imodzi, yokhala ndi sensor yolondola kwambiri komanso chip chotolera kwambiri.
●Makinawa mumalowedwe ndi njira yamanja yosankha.
●Sonyezani voteji ya HV, voteji ya LV, LV yapano, nthawi, ndi zotsatira zokhazikika.
●Kutetezedwa kopitilira muyeso komanso kupitilira apo.Mphamvu yotulutsa, malire apamwamba a HV, malire apamwamba a LV ndi nthawi zitha kukhazikitsidwa.
●Zero-kuyambira ntchito.Kuyesa kutha kupitilira mphamvu yamagetsi ikabwerera ku zero.
●Sungani mpaka 8000pcs data m'miyezi itatu.Ili ndi doko la USB kuti ikweze deta ku disk ya USB.
●Kuyika voliyumu ikafika, izikhala nthawi yokha.Pambuyo pa nthawi, mphamvu yamagetsi ibwerera ku ziro.
●Mphamvu ya LV ikatha kuyika mtengo, voliyumu idzadulidwa yokha ndipo ibwerera ku ziro.Mphamvu ya HV ikatha kuyika mtengo, chinthu choyeseracho chimadulidwa ndipo kuyesa kumatha kupitilirabe.
●Ndi mphamvu yotsutsa kusokoneza, yoyenera chilengedwe cha electromagnetic.
●Ndi mawilo a unit control unit ndi HV unit, yosavuta kusuntha.
Control unit specifications
●Mphamvu: AC380V, 50/60Hz
●Mphamvu: 30kVA
●Mphamvu yamagetsi: AC 0-430V
●Adavoteledwa pano: 75A
●Chiyerekezo chamakono okonzedwanso osiyanasiyana: 0-75A
●HV voltmeter osiyanasiyana: 0-200kV
●Kulondola: 1.5% ya kuwerenga ± 1digit (FS)
●HV ammeter osiyanasiyana: 0-100mA
●Kulondola: 1.5% ya kuwerenga ± 1digit (FS)
●LV ammeter osiyanasiyana: 0-25A
●Kulondola: 2.0% ya kuwerenga ± 1digit (FS)
●Nthawi yofikira: 1s-99h
●Kulemera kwake: pafupifupi 116kg
●Kukula: 520mm (L) * 460mm (W) * 1140mm (H)
Mayeso a transformer (HV unit)
●Mphamvu yolowera: 0-400V
●Zolowetsa panopa: AC 0-75A
●Mphamvu yamagetsi: AC 0-200kV, DC 0-200kV
●Zotulutsa zamakono: AC 150mA, DC 106mA
●Mphamvu: 30kVA
●HV mbali / LV kutembenuka kwa mbali: 500:1
●Kuyeza mphamvu: AC 0-100V
●Kulondola: 1.5% ya kuwerenga ± 1 manambala (FS)
●Palibe katundu pano: <10%
●Mphamvu yamagetsi: <10%
●Kulemera kwake: pafupifupi 180kg
●kukula: 630mm(D)*1730mm(H)
Mikhalidwe yogwirira ntchito
●Malo ogwirira ntchito: Palibe gasi, nthunzi, fumbi lamankhwala komanso zida zophulika komanso zowononga zomwe zingakhudze kutsekeka.
●Kutentha kwa chilengedwe: -20-50 ℃.
●Chinyezi cha chilengedwe: ≤85% RH (palibe condensing).