GDCO-301 Paintaneti Monitoring Dongosolo Lozungulira Panopa pa Cable Sheath
Zingwe zomwe zili pamwamba pa 35kV ndi zingwe zokhala ndi chitsulo chimodzi.Popeza kuti chingwe chachitsulo chachitsulo chimodzi chimakhala ndi chingwe cha maginito chomwe chimapangidwa ndi AC panopa mu waya wapakati, mbali ziwiri za chingwe chimodzi chokhala ndi magetsi okwera kwambiri.Chifukwa chake, njira zoyenera zoyatsira ziyenera kuchitidwa kuti magetsi asungidwe mkati mwa voteji yotetezeka (nthawi zambiri osapitilira 50V, koma osapitilira 100V ndi njira zachitetezo).Nthawi zambiri, chingwe chachitsulo chachifupi cha single-core chingwe chimakhazikika kumapeto kwina ndikuzikika kudzera mumpata kapena chitetezo chopinga kumapeto kwina.Chingwe chachitsulo chamzere wautali umodzi - chingwe chapakati chimakhazikitsidwa ndi kugwirizana kwa magawo atatu.Ziribe kanthu kuti ndi njira yanji yokhazikitsira pansi, kutchinjiriza bwino kwa sheath ndikofunikira.Pamene kusungunula kwa chingwe kumawonongeka, chitsulo chachitsulo chidzakhazikika pazigawo zingapo, zomwe zidzapangitse kuyendayenda, kuonjezera kutayika kwa sheath, kukhudza mphamvu yonyamula chingwe, komanso kuchititsa kuti chingwe chiwotchedwe. chifukwa cha kutentha kwambiri.Pa nthawi yomweyo, kutsimikizira mkulu voteji chingwe zitsulo m'chimake grounding mwachindunji kulumikiza malo n'kofunika kwambiri, ngati nthaka mfundo sangathe mogwira maziko pazifukwa zosiyanasiyana, chingwe zitsulo m'chimake kuthekera adzauka kwambiri kuti kilovolts angapo ngakhale masauzande volts. , n'zosavuta kutsogolera kuwonongeka kwa m'chimake ndi kutuluka kosalekeza, kuchititsa kukwera kwa kutentha kwa chingwe chakunja kapena kuyaka.
GDCO-301 imagwiritsa ntchito njira yozungulira.Pamene single-core chingwe zitsulo m'chimake ali pansi pa zinthu zabwinobwino (ie, mfundo imodzi grounding), kuzungulira panopa m'chimake, makamaka capacitive panopa, ndi yaying'ono kwambiri.Kamodzi kokhala ndi mfundo zambiri kumapezeka pazitsulo zachitsulo ndikupanga chipika, kuyendayenda kwamakono kudzawonjezeka kwambiri ndipo kumatha kufika kupitirira 90% ya panopa.Kuwunika kwanthawi yeniyeni kwa kayendedwe kachitsulo kachitsulo ndi kusintha kwake kumatha kuzindikira kuwunika kwapaintaneti kwa zolakwika zamitundu ingapo zachitsulo chachitsulo chachitsulo chimodzi, kuti mupeze nthawi yake komanso molondola kuti dziko lapansi lili ndi vuto, pewani kuchitika kwa ngozi ya chingwe komanso onetsetsani ntchito yotetezeka komanso yodalirika.
Imagwiritsa ntchito GSM kapena RS485 ngati njira yolumikizirana.Ndizoyenera kuyang'anira zolakwika zamitundu yambiri pazingwe zapakati pa 35kV.
GDCO-301 Online Monitoring System of Curling Current pa Cable Sheath imaphatikizapo: unit yaikulu ya Integrated monitoring device ndi transformer yamakono, kutentha ndi anti-kuba sensor.Mtundu wotseguka wa transformer wamakono umayikidwa pamtunda wa chingwe cha sheath ndipo umasinthidwa kukhala chizindikiro chachiwiri chisanayambe chipangizo chowunikira.Sensa ya kutentha imagwiritsidwa ntchito poyang'anira kutentha kwa chingwe, ndipo sensa yotsutsana ndi kuba imagwiritsidwa ntchito poyang'anira mzere wozungulira.Kapangidwe ka makina owunikira pa intaneti a cable sheath ndi motere:
●Kuyang'anira nthawi yeniyeni ya mphamvu yapansi ya chingwe chachitatu chagawo, mphamvu yonse yapansi ndi mphamvu yogwiritsira ntchito chingwe chachikulu cha gawo lililonse;
●Kuwunika nthawi yeniyeni ya kutentha kwa chingwe cha magawo atatu;
●Real-time anti - kuwunika kwa kuba kwa kuyatsa kwa chingwe;
●Nthawi ya nthawi ikhoza kukhazikitsidwa;
●Zigawo za alamu komanso ngati zowunikira zofananira zimaloledwa kupanga alamu zitha kukhazikitsidwa;
●Khazikitsani mtengo wapamwamba, mtengo wocheperako komanso mtengo wapakati pa nthawi yokhazikitsidwa;
●Kuwunika kwenikweni kwa chiŵerengero chapamwamba ndi mtengo wocheperapo wa gawo limodzi la pansi pakali pano mkati mwa nthawi yowerengera, ndi kukonza alamu;
●Kuwunika kwanthawi yeniyeni kwa chiŵerengero cha pansi pakali pano kuti chiyike mkati mwa nthawi yowerengera, ndi kukonza alamu;
●Kuwunika kwenikweni kwa kusintha kwa kusintha kwa gawo limodzi pakali pano mkati mwa nthawi yowerengera, ndi kukonza alamu;
●Deta yoyezera imatha kutumizidwa nthawi iliyonse.
●Itha kufotokozera gawo limodzi kapena zingapo zowunikira ku alamu, kutumiza chidziwitso cha alamu ku foni yosankhidwa;
●Kuyeza nthawi yeniyeni yamagetsi olowera;
●Zonse zowunikira zimakhala ndi zolemba za nthawi kuti zitsimikizire kuti deta ndi yapadera;
●Zowunikira zonse zowunikira zimatha kukhazikitsidwa malinga ndi zomwe wogwiritsa ntchito akufuna;
●Njira zingapo zotumizira deta: mawonekedwe a RS485, GPRS, GSM SMS, amatha kugwiritsa ntchito njira imodzi kapena zingapo zotumizira nthawi imodzi;
●Thandizani kukonza kwakutali ndi kukweza;
●Mapangidwe ogwiritsira ntchito mphamvu zochepa, amathandizira kuyika kwamphamvu kosiyanasiyana: CT induction power, AC-DC mphamvu ndi mphamvu ya batri;
●Ndi zigawo mafakitale kalasi, ndi kudalirika wabwino & bata;
●Ma module otsekedwa mokwanira, osavuta kuyika, njira zotsekera zimatengedwa pazigawo zonse, magwiridwe antchito abwino oletsa kugwedezeka, komanso osavuta kusintha ndi kugawa;
●Thandizani IP68 chitetezo mlingo.
Kanthu | Parameters | |
Panopa
| Panopa ntchito | 1 njira, 0.5~1000A (Ikhoza kusinthidwa) |
Sheath pansi panopa | 4 njira, 0.5~200A (Ikhoza kusinthidwa) | |
Kulondola kwa miyeso | ±(1%+0.2A) | |
Nthawi yoyezera | 5~200s | |
Kutentha | Mtundu | -20 ℃~+ 180 ℃ |
Kulondola | ±1℃ | |
Nthawi yoyezera | 10~200s |
Mtengo wa RS485
●Baud mlingo: 2400bps, 9600bps ndi 19200bps akhoza kukhazikitsidwa.
●Kutalika kwa data: 8 bit:
●Yoyamba pang'ono: 1 pang'ono;
●Kuyimitsa pang'ono: 1 pang'ono;
●Calibration: palibe calibration;
GSM/GPRS port
●Mafupipafupi ogwira ntchito: Quad-band, 850 MHz / 900 MHz / 1800 MHz / 1900 MHz;
●GSM Chinese / English mauthenga achidule;
●GPRS kalasi 10, Max.kutsitsa liwiro 85.6 kbit/s, Max.kukweza liwiro 42.8 kbit/s, kuthandizira TCP/IP, FTP ndi HTTP protocol.
Magetsi
Mphamvu ya AC
●Mphamvu yamagetsi: 85 ~ 264VAC;
●pafupipafupi: 47 ~ 63Hz;
●Mphamvu: ≤8W
Batiri
●Mphamvu yamagetsi: 6VDC
●Kuthekera: kumatsimikiziridwa ndi nthawi yogwira ntchito ya batri
●Kugwirizana kwa batri
Electrostatic discharge chitetezo | Kalasi 4:GB/T 17626.2 |
Kutetezedwa kwa ma radio-frequency electromagnetic field radiation chitetezo | Kalasi 3:GB/T 17626.3 |
Kutetezedwa kwamagetsi kwanthawi yayitali / kuphulika | Kalasi 4:GB/T 17626.4 |
Kuchulukitsa chitetezo chokwanira | Kalasi 4:GB/T 17626.5 |
Radio-frequency field inductive conduction chitetezo | Kalasi 3:GB/T 17626.6 |
Mphamvu pafupipafupi maginito chitetezo chokwanira | Kalasi 5:GB/T 17626.8 |
Pulse magnetic field chitetezo | Kalasi 5:GB/T 17626.9 |
Damping oscillation maginito chitetezo chokwanira | Kalasi 5:GB/T 17626.10 |
Reference standard:
Q/GDW 11223-2014: Tsatanetsatane waukadaulo pakuzindikiritsa boma pamizere yamagetsi apamwamba
4.1 Kuzindikira kwamtundu wa chingwe kumatha kugawidwa m'magulu awiri: kuzindikira pa intaneti komanso kuzindikira popanda intaneti.Zoyamba zimaphatikizanso kuzindikira kwa infrared, kuzindikira kwaposachedwa kwa sheath ya chingwe, kuzindikira kutulutsa pang'ono, pomwe kuwonekera kwapaintaneti kumakhala ndi kutulutsa pang'ono kwapang'onopang'ono kuyesedwa kwa resonant, oscillation cable partial discharge.
4.2 Njira zodziwira mawonekedwe a chingwe zimaphatikizapo kuyesa kwachirengedwe pamlingo waukulu, kuyesanso zizindikiro zokayikiridwa, kuyesa kuyang'ana pa zida zolakwika.Mwanjira imeneyi, ntchito yabwinobwino ya chingwe imatha kutsimikizika.
4.3 Ogwira ntchito zofufuza akuyenera kupita ku maphunziro aukadaulo ozindikira chingwe ndikukhala ndi ziphaso zina.
4.4 Zomwe zimafunikira pa chojambula cha infrared ndi chojambulira chapansi pano zikunena Zakumapeto A. Zomwe zimafunikira pakuzindikira kutulutsa kwamagetsi kwamphamvu kwambiri, kuzindikira kwapang'onopang'ono kwamagetsi amagetsi komanso chowunikira cha akupanga kutulutsa pang'ono kumatanthawuza Q/GDW11224-2014.
4.5 Magwiritsidwe osiyanasiyana amatengera Table 1.
Njira | Voltage kalasi ya chingwe | Kuzindikira kofunikira | Chilema | Pa intaneti / pa intaneti | Ndemanga |
Thermal infrared chithunzi | 35kV ndi pamwamba | Terminal, cholumikizira | Kulumikizana kosasunthika, kunyowa, cholakwika cha insulation | Pa intaneti | Mokakamizika |
Metal sheath pansi pano | 110kV ndi kupitilira apo | Grounding system | Kuwonongeka kwa insulation | Pa intaneti | Mokakamizika |
Kutulutsa pafupipafupi pang'ono | 110kV ndi kupitilira apo | Terminal, cholumikizira | Kuwonongeka kwa insulation | Pa intaneti | Mokakamizika |
Kutulutsa kwapang'onopang'ono kwambiri | 110kV ndi kupitilira apo | Terminal, cholumikizira | Kuwonongeka kwa insulation | Pa intaneti | Zosankha |
Ultrasonic wave | 110kV ndi kupitilira apo | Terminal, cholumikizira | Kuwonongeka kwa insulation | Pa intaneti | Zosankha |
Kutulutsa pang'ono pansi pa mayeso a frequency frequency resonant | 110kV ndi kupitilira apo | Terminal, cholumikizira | Kuwonongeka kwa insulation | Zopanda intaneti | Mokakamizika |
OWTS oscillation chingwe kutulutsa pang'ono | 35 kv | Terminal, cholumikizira | Kuwonongeka kwa insulation | Zopanda intaneti | Mokakamizika |
Table 1
Mphamvu yamagetsi | Nthawi | Ndemanga |
110(66)kV | 1. Mkati mwa mwezi wa 1 mutatha opaleshoni kapena kukonza kwakukulu 2. Kamodzi kwa miyezi ina itatu 3. Ngati pakufunika | 1. Nthawi yodziwikiratu ifupikitsidwe pakakhala katundu wolemetsa pazingwe kapena nthawi yachilimwe. 2. Kuzindikira kuyenera kuchitika pafupipafupi potengera malo ogwirira ntchito, zida zakale, ndi zida zosokonekera. 3. Kusintha koyenera kuyenera kupangidwa malinga ndi momwe zida zilili komanso malo ogwirira ntchito. 4. Njira yowunikira pa intaneti yaposachedwa pa chingwe sheath imatha kusintha mawonekedwe ake amoyo. |
220 kV | 1. Mkati mwa mwezi wa 1 mutatha opaleshoni kapena kukonza kwakukulu 2. Kamodzi kwa miyezi ina itatu 3. Ngati pakufunika | |
500 kV | 1. Mkati mwa mwezi wa 1 mutatha opaleshoni kapena kukonza kwakukulu 2. Kamodzi kwa miyezi ina itatu 3. Ngati pakufunika |
Table 4
5.2.3 Njira zodziwira matenda
Ndikofunikira kuphatikizira katundu wa chingwe ndi zomwe zikuchitika pano za sheath ya chingwe ndi kuyeza kwa chingwe sheath.
Njira zodziwira matenda zimatengera Table 5.
Yesani | Zotsatira | Malangizo |
Ngati zonse zomwe zili pansipa zikukwaniritsidwa: 1. Mtheradi wamtengo wapatali wapansi<50A; 2. Chiŵerengero cha pakati pa nthaka ndi katundu<20%; 3. Max.mtengo/ Min.mtengo wa single phase ground current<3 | Wamba | Gwirani ntchito monga mwachizolowezi |
Ngati chosowa chilichonse chili pansipa chikukwaniritsidwa: 1. 50A≤mtengo wapatali wa nthaka panopa ≤100A; 2. 20%≤chiŵerengero chapakati pa nthaka ndi katundu ≤50%; 3. 3≤Max.mtengo/Mphindi.mtengo wa single phase ground current≤5; | Chenjezo | Limbikitsani kuwunika ndikufupikitsa nthawi yozindikira |
Ngati chosowa chilichonse chili pansipa chikukwaniritsidwa: 1. Mtheradi wamtengo wapatali wapansi>100A; 2. Chiŵerengero cha nthaka panopa ndi katundu>50%; 3. Max.mtengo/Mphindi.mtengo wa single phase ground current>5 | Chilema | Yatsani ndikuwunika. |
Table 5